How to Choose the Right Diesel Generator Size in Saudi Arabia

Power Systems shows here everything you need to size a generator: converting kVA to amps and kW, diesel consumption for every model, and how many air conditioners each generator runs.

The quick rule: in a three-phase 380 V system, 1 kVA ≈ 1.5 A and 1 kVA ≈ 0.8 kW. So a 30 kVA generator delivers about 46 A and runs roughly 6 × 18,000 BTU air conditioners.

kVA to Amps and kW Conversion

  • 1 kVA (3-phase, 380 V) ≈ 1.5 A
  • kW = kVA × 0.8 ; kVA = kW ÷ 0.8
  • 1 HP ≈ 0.75 kW ≈ 0.93 kVA
kVAAmps (3-phase, 380 V)kW (at 0.8 power factor)
1015 A8 kW
1523 A12 kW
2030 A16 kW
2538 A20 kW
3046 A24 kW
4061 A32 kW
5076 A40 kW
6091 A48 kW
75114 A60 kW
100152 A80 kW
125190 A100 kW
150228 A120 kW
200304 A160 kW
250380 A200 kW
300456 A240 kW
350532 A280 kW

Generator Size Calculator

Calculate the Right 3-Phase Generator Size

Calculations assume 380V / 60Hz three-phase power, matching our full product range.

Enter your total load to see the result

This tool provides an estimate for guidance only. Please contact our team to confirm the exact specification for your project.

How Many Air Conditioners Does Each Generator Run?

Please note: These figures are general estimates for initial guidance only. Actual load depends on the AC brand and age, inverter vs. non-inverter compressor, ambient temperature, start-up surge, and every other connected load. The correct generator size for any specific installation must be confirmed by a qualified electrician or the Power Systems team before ordering.
ModelPrime kVA18,000 BTU units24,000 BTU units
KT1110.91
KT1514.821
KT181832
KT232343
KT272764
KT3333.575
KT3636.276
KT5050118
For larger projects and requirements outside this range, use the calculator above or contact our team.

Diesel Consumption by Generator Size

ModelPrime kVAat 100% of prime powerat 75% of prime powerat 50% of prime powerat 25% of prime power
KT1110.92.6 L/h1.95 L/h1.3 L/h0.65 L/h
KT1514.83.5 L/h2.63 L/h1.75 L/h0.87 L/h
KT18183.9 L/h2.925 L/h1.95 L/h0.975 L/h
KT23235.2 L/h3.9 L/h2.6 L/h1.3 L/h
KT27276.2 L/h4.65 L/h3.1 L/h1.55 L/h
KT3333.57.9 L/h5.925 L/h3.95 L/h1.975 L/h
KT3636.27.9 L/h5.925 L/h3.95 L/h1.975 L/h
KT505011.8 L/h9 L/h6.7 L/h4.9 L/h
DT3533.58 L/h6.4 L/h4.4 L/h2.7 L/h
DT4546.511.7 L/h9.2 L/h6.4 L/h4 L/h
DT575715.8 L/h12.2 L/h8.65 L/h4.9 L/h
DT656515.8 L/h12.2 L/h8.65 L/h4.9 L/h
DT9091.221 L/h16 L/h11 L/h6.3 L/h
DT115113.527 L/h20.2 L/h14.5 L/h8.2 L/h
DT130131.831.4 L/h23.9 L/h16.9 L/h8.5 L/h
DT15515534.5 L/h25.5 L/h17.2 L/h8.5 L/h
DT17017037.4 L/h27.9 L/h18.7 L/h9.3 L/h
DT21021048.5 L/h37 L/h24.2 L/h12.8 L/h
DT26026153 L/h41 L/h28 L/h15.5 L/h
DT29029072 L/h60 L/h42 L/h21.5 L/h
DT32032072 L/h60 L/h42 L/h21.5 L/h
CT545414 L/h11 L/h8 L/h5 L/h
CT686818 L/h13 L/h9 L/h5 L/h

* Litres per hour at the prime rating, ~0.8 power factor. Actual consumption varies with load profile, ambient temperature and engine condition.

How to Size Your Generator: Step by Step

  1. List every appliance the generator will run and its maximum wattage.
  2. Add up the watts to get the total load.
  3. Divide by the power factor (0.8) to convert kW to kVA. See the load calculation and formula page.
  4. Add a 25% safety margin for starting loads.
  5. Pick a generator where the continuous load stays between 50% and 75% of the prime rating. Above 75% overloads the set; running below 50% for long periods causes carbon build-up and cylinder glazing (wet stacking) that damages the engine.
  6. Browse the Kubota, John Deere and Cummins models or request a quote.

Frequently Asked Questions

How many amps is 1 kVA?

In a three-phase 380 V system, 1 kVA ≈ 1.5 A. So a 30 kVA generator delivers about 46 A, and a 100 kVA generator about 152 A.

How many kW is a 3-phase generator?

Multiply the kVA rating by the power factor (typically 0.8 for diesel gensets) to get kW. A 30 kVA generator ≈ 24 kW; a 50 kVA generator ≈ 40 kW.

How much diesel does a generator use per hour?

It depends on the rating and how heavily it is loaded. A Kubota 18 kVA uses about 2.9 L/hour at 75% load; a 50 kVA about 9 L/hour. See the fuel consumption table on this page for every model.

How many air conditioners will a 20 kVA generator run?

A Kubota 18–20 kVA generator (KT18) runs up to 3 × 18,000 BTU split units, or 2 × 24,000 BTU units, keeping the load at 75% of the prime rating. These are general estimates and should be confirmed by a qualified technician.

How many amps is a 100 kVA generator?

A 100 kVA generator in a three-phase 380 V system delivers about 152 A, and is equivalent to roughly 80 kW at a 0.8 power factor.